 F.A. Signals/Sirens :

 Number of readers : 6694
 
Conventional:
 
Visual and Audible Signals
 

 FH-240

SELECT-A-HORN SERIES

 

Description

     Mircom’s Series 200 Select-a-Horn are designed to comply with NFPA/ANSI audible emergency evacuations signal and UL 464/ ULC S525 audible signaling appliances. The Horn provides two different field selectable tones and a High/Low output setting that can be accomplished with the use of mini jumpers located on back of the unit. The horn is clearly labeled with FIRE lettering and is polarized for connecting to supervised fire alarm circuits. The Series 200 Select-a-Horn is available in red or white housing 24V DC models. The horn signals are listed for indoor use, ceiling and wall mount.

 

Application

    The Series 200 Horns are recommended for use in areas such as meeting rooms, schools, corridors, apartments, office buildings, restaurants, hotels and any other application where effective audible warning is required by Federal, Provincial, State or local authority having jurisdiction.

 

Engineering Specifications

     The Audible alarm indicating appliance shall be Mircom model FH-240 or equivalent device. The horn shall be listed under UL 464/ ULC S525 standard for Audible Signaling Appliance and shall be approved for fire protective service. The sound output shall be field selectable. The Horn shall provide two different field selectable tones as well as a High and Low field selectable sound output setting. The signaling Select-a-Horn Horn shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The Horn shall be capable of WALL or CEILING mounting to a universal backbox. The FH-240 shall be installed as per plans and specifications.
 

Features

- Designed to meet or exceed NFPA/ANSI Standards and UL 464/ULC S525 Audible Signal Appliance.
- UL/ULC listed for Wall or Ceiling mount
- Screw terminal capacity up to 12 AWG
- Universal mounting plate included with each unit
- 24VDC with two field selectable settings
- Polarized with wide listed voltage ranges using filtered DC or unfiltered FWR input voltage
- Horn field selectable tones: -3000 Hz interrupted or Electro-mechanical -Temporal or Non-temporal -High or Low dBA output
- All models mount to 4 inch square, single gang, double gang or octagon backbox
- Available in red or white housing
- Synchronization requires an SDM-240 Sync Module

 

FHS-240

SELECT-A-HORN/STROBE SERIES

 

Description

     Mircom’s Series 200 Select-a-Horn/Strobe are designed to comply with the Americans with Disability Act (ADA) and meet UL standard 1971/ULC S526 requirements for emergency signaling devices for the hearing impaired. The Series 200 Select-A Horn/Strobe features a unique candela intensity field selector switch for switching the candela output from 15/75 to 30/120 cd. The Horn provides two different field selectable tones and a High/Low output setting that can be accomplished with the use of mini jumpers located on the back of the unit. The Strobe housing is clearly labeled with vertical “FIRE” lettering and is polarized for connecting to supervised fire alarm circuits. The Strobe is designed with a xenon flashtube and provides a candela intensity tamper-proof field selector switch for maximum performance.

     The Select-A-Horn/Strobe series is available in red and white housing 15/75 or 30/120 cd. 24VDC models. The Series 200 Select-a-Strobe can be synchronized by using the SDM-240 sync module to comply with NFPA recommendations concerning photosensitive epilepsy when installing 2 or more visual appliances within the field of view. The strobe signals are listed for indoor use, ceiling and wall mount, under UL1971/ULC S526 standards.
 

Application

      The Series 200 Horn/Strobes are recommended for use in areas such as meeting rooms, schools, corridors, apartments, office buildings, restaurants, hotels and any other application where effective visual warning is required by Federal, Provincial, State or local authority having jurisdiction.

Features
- Designed to meet NFPA/ANSI Standards
- Designed to meet UL 464/ULC S525 Audible Signal Appliance
- UL /ULC listed for Wall or Ceiling mount
- Screw terminal capacity up to 12 AWG
- Universal mounting plate included with each unit
- Strobe with two field selectable settings 15/75 or 30/120cd
- UL listed for fire protective service
- Polarized strobes with wide listed voltage ranges using filtered DC or unfiltered FWR input voltage
- Horn field selectable tones: -3000 Hz interrupted or Electro-mechanical -Temporal or Non-temporal -High or Low dBA output
- Meets ADA guidelines for minimum one flash per/sec (1 Hz)
- All models mount to 4 inch square backbox
- Tamper-proof candela selector switch
- Synchronization requires an SDM-240 Sync Module
- Available in red or white housing

Engineering Specifications

     The visual alarm indicating appliance shall be MIRCOM model FHS-240W/FHS-240R or equivalent device. The Strobe shall be listed under UL 1971/ ULC S526 standards for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela output shall be field selectable, having a dual setting of 15/75 cd or 30/120 cd output. The Horn shall provide two different field selectable tones as well as a High and Low field selectable sound output setting. The signaling Horn/ Strobe shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to produce a signal flash per second with continuously applied minimum voltage. The Horn/Strobe shall be capable of WALL or CEILING mounting to a universal backbox. Visual signaling devices shall be mounted 80 inches above the highest floor point or 6 inches below ceiling; whichever is lowest and are to be installed as per plans and specifications.

FS-240

SELECT-A-STROBE SERIES

Description

     Mircom’s Series 200 Select-a-Strobe are designed to comply with the Americans with Disability Act (ADA) and meet UL standard 1971/ ULC S526 requirements for emergency signaling devices for the hearing impaired. The Series 200 Select-a-Strobe features a unique candela intensity field selector switch for switching the candela output from 15/75 to 30/120 cd. The strobe is polarized for connecting to supervised fire alarm circuits and is designed with a xenon flashtube. The strobe provides a candela intensity tamper-proof field selector switch for maximum performance. The Series 200 Select-a-Strobe can be synchronized by using the SDM-240 sync module to comply with NFPA recommendations concerning photosensitive epilepsy when installing 2 or more visual appliances within the field of view. The strobe signals are listed for indoor use, ceiling and wall mount, under UL1971/ULC S526 Standards.
 

Engineering Specifications

     The visual alarm indicating appliance shall be MIRCOM model FS-240W/FS-240R or equivalent device. TheStrobeshallbelistedunderUL1971/ULC S526 standards for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela output shall be field selectable, having a dual setting of 15/75 cd or 30/120 cd output. The signaling strobe shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to produce a signal flash per second with continuously applied minimum voltage. The strobe shall be capable of WALL or CEILING mounting to a universal backbox. Visual signaling devices shall be mounted 80 inches above the highest floor point or 6 inches below ceiling; whichever is lowest and are to be installed as per plans and specifications.

Features
- Designed to meet or exceed NFPA/ANSI Standards
- Designed to meet or exceed UL 464/ULC S526 Audible Signal Appliance
- UL/ULC listed for Wall or Ceiling mount
- Screw terminal capacity up to 12 AWG
- Universal mounting plate included with each unit
- Strobe with two field selectable settings 15/75 or 30/120cd
- UL listed for fire protective service
- Polarized strobes with wide listed voltage ranges using filtered DC or unfiltered FWR input voltage
- Meets ADA guidelines for minimum one flash per/sec (1 Hz)
- All models mount to 4 inch square backbox
- Tamper-proof candela selector switch
- Synchronization requires an SDM-240 Sync Module
- Available in Red or White Housing

 

BL-SERIES

MOTOR BELLS 

Description

     Mircom’s BL-Series of motor driven bells are designed for today’s fire alarm applications. The durable steel construction provides loud resonant tones necessary for fire alarm installations. The new BL-Series bells use a varistor suppression element to prevent RFI and EMF noise problems to modern fire alarm control panels.

The motor used on the BL-Series operates at a very low current (15 mA) to maximize the number of bells per circuit. A common mounting plate on both the 6 and 10 inch diameter bells facilitates interchanging bell sizes. A solid aluminum base completely houses the bell mechanism.

Features

- Low current draw (15 mA)
- 6 and 10 inch diameter steel shells for long term reliability
- RFI and EMF suppression prevents noise problems to the fire alarm control panel
- Polarized for DC supervision
- Red finish

 

SHB24-75 SERIES

OUTDOOR HORN/STROBE COMBINATION 

Description

      The SHB24-75 series outdoor Horn/Strobe is a high performance, high intensity, solid state 24V DC appliance. It features prominent visibility, distinguished reliability and a long operating life. The horn provides a selectable continuous tone or temporal pattern (code 3). With the use of the SDM-240 Sync Module, the horn/strobe can be configured to provide a synchronized temporal horn (code 3) and strobe flash. This configuration allows for the horn to be silenced while the strobe remains active.

The strobe light is UL 1638 Approved, and is listed for visual signaling appliances private mode, emergency and general utility signaling for use in outdoor applications. The ready-to-use outdoor DC powered Horn/Strobe is designed for audible and visual notification in fire alarm applications, and can be interfaced with pull stations, flow switches and sprinkler systems for use in residential, commercial, and industrial applications. Alternatively it can be installed as a stand alone unit.

The SHB24-75 outdoor Horn/Strobe is designed to provide emergency warning when connected to a 24V DC source. It is specifically designed to meet or exceed existing and evolving code requirements.

The SHB series Horn/Strobe is recommended for use in outdoor applications such as: schools, restaurants, warehouses, malls and any other application where effective audible and visual warning is required. Installations must comply in accordance with applicable standards and meet all state and local electrical codes and approved by the authority having jurisdiction.

Features

- Designed to meet NFPA / ANSI Standards

  and ADA Accessibility Guidelines

- Wire leads for in/out field wiring

- Strobe flash at 1 flash per second

- 75 candela intensity

- Low current draw

- Concealed mounting screws

- Optional weather-proof back box (SBX-1)

- Available lens colors: Blue, Clear, Green, Red

Engineering Specifications

     The audible and visual alarm indicating appliance shall be a model SHB24-75 or equivalent device. The Strobe shall be listed in compliance with UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela output shall be 75 candela. The SHB24-75 shall be listed in compliance with UL 1638 Visual Appliance Private Mode Emergency and General Utility for use in Indoor/Outdoor applications. The signaling Horn/Strobe shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to produce one signal flash per second with continuously applied minimum voltage. The Horn/Strobe shall be capable of WALL mounting to an SBX-1 weather proof back box. Audible and Visual signaling devices shall be installed as per plans and specifications.

 

 